How to Size a Wire for a Subpanel

Adding a subpanel - for a garage, workshop, addition, or detached structure - starts with correctly sizing the feeder wire that supplies it. Undersized feeders overheat and fail inspection; oversized feeders waste money. This guide walks through the checks that determine minimum wire size.

Step 1: Determine the subpanel's total load

Add up the continuous and non-continuous loads the subpanel will serve - lighting circuits, receptacles, any dedicated appliance circuits (like a shop tool or EV charger). For a simple garage or workshop subpanel, many electricians size for the panel's full bus rating (e.g. a 60A or 100A subpanel) rather than a detailed connected-load tally, especially when future expansion is likely.

Step 2: Check ampacity against the feeder breaker

The feeder conductor's ampacity (corrected for ambient temperature and any conductor bundling - see the Wire Ampacity Calculator) must be at least equal to the feeder breaker size at the main panel. A 60A subpanel feeder breaker requires conductors rated for at least 60A after all correction factors are applied.

Step 3: Check voltage drop over the feeder run

Long feeder runs - common for detached garages or workshops - are frequently limited by voltage drop rather than ampacity. Use the Wire Size Calculator with your subpanel's expected load current, the one-way distance to the subpanel, and a 3% maximum drop target, then compare the result against the ampacity-driven minimum from Step 2 and use whichever is larger.

Step 4: Don't forget the grounding and neutral conductors

A subpanel fed from the same structure typically requires an insulated (not bonded) neutral and a separate equipment grounding conductor run alongside the feeders - bonding neutral and ground at a subpanel, as is done at the main panel, is a common and dangerous code violation that creates parallel neutral return paths.

Frequently Asked Questions

Can I use the subpanel's rated bus size instead of calculating actual load?

Yes, this is common practice for garages, workshops and additions where future load growth is likely - it's a conservative approach that avoids undersizing if more circuits are added later.

Does the subpanel breaker size need to match the panel's main breaker?

No - the feeder breaker at the main panel just needs to protect the feeder conductors and not exceed the subpanel's bus rating; it's often smaller than the subpanel's full rated capacity.

What wire size is typical for a 100A subpanel feeder?

A common minimum is #4 AWG copper or #2 AWG aluminum at short distances - but always verify with the Wire Size Calculator using your actual distance, since longer runs often require larger conductors for voltage drop.